The data supplied below is an example of the PCS1’s actual performance near Jacksonville,
Florida during 1989. It can be observed that the PCS1 raised the pool’s temperature from 3 to 8º F
in a single day. A more typical rise in the pool’s temperature is 1 to 2º F per day. Thus, over the
course of two weeks, the pool is raised to the desired swimming temperature. The pool in the
example below used a pool blanket during periods of extended non-use.
The format provided below is a good one to use for determining the overall performance of
the PCS1 in your own installation. Take the temperature readings at the same time each morning
[7-9 a.m.] and each afternoon [4-6 p.m.].
Date
4/19
4/20
4/21
4/22
4/23
4/24
4/25
4/26
4/27
5/2
5/2
Air Temp
87
80
74
83
85
88
90
90
90
84
80
Conditions
Sunny
Overcast
Cloudy
Sunny
Sunny
Sunny
Sunny
Sunny
Sunny
Sunny
Sunny
Pool ºF a.m.
82
85
---
83
86
87
89
90
96
84
86
Pool ºF p.m.
87
88
86
88
91
92
94
98
stopped heat
90
91
ºF Gained
5
3
---
5
5
5
5
8
What is the PCS1 capable of doing? The following curves show designed verified
performance. The performance curves assume constant temperature differentials. In reality, the
temperature differentials will vary somewhat throughout the course of the solar heating day.
These operating curves show the heat transfer range of the PCS1. By knowing the flow
rate in gallons per minute, the attic's temperature and the pool's temperature -- both the BTU
hourly rate of heat transfer and the output rise in degrees Fahrenheit from the PCS1 can be
Example: If the flow rate is 30 gpm and the temperature differential between the attic and
the swimming pool is 32º F, the output rise will be approximately 4º F [PCS1 output temperature
minus input temperature]. This can be found by simply locating the flow rate on the horizontal
scale and going up vertically on the graph until you find the curve with the correct temperature
differential between the attic and the pool. Discussion continues on the next page.
This is the attic temperature minus the swimming pool temperature. Then, simply draw a
horizontal line to the left scale from the curve and read the output rise in ºF. An example of a 32º F
temperature differential is an attic at 110º F and a swimming pool at 78º F.
Observe that as flow rate decreases for a given and constant temperature differential that the
output in º F will increase. Conversely, as flow rate increases, output temperature in º F will
decrease. The amount of heat transfer, however, is the same in both instances as long as the
temperature differential remains constant and is governed by the formula BTUS = 500 x ∆T x
GPM. The constant 500 is derived from the weight of water at 8.34 pounds per gallon times the
factor 60 used to convert the heat transfer to an hourly rate.
Observe also that as the temperature differential increases between the attic and the pool that
the rate of heat transfer also increases. The attic temperature should be measured inside the attic at
or near its peak. Once operating, the PCS1 will stratify the attic with lower temperatures at the attic
floor and higher temperatures at its peak. The PCS1 will simply take the solar radiation off the
inside of the roof at the same time it emanates into the attic. The roof will function as a massive