SECTION 3 - INSTALLATION

Page S3-37

CAUTION: Some pool pumps were sized smaller and set up to run 24 hours per day for proper

IMAGE PCS1_MANUAL67.gif

filtration. If the pool water is getting cloudy and a timer is not used, manual operation of the pump

may be required for proper filtration. Or, the pump may be upgraded to provide proper filtration

without running 24 hours a day. See discussion on pump sizing in “Common Questions.”

14. Use a separate circuit breaker for the pool’s support system, which includes power to

the LX220 and the PCS1 via the LX220.

15. The LX220 is UL listed.

16. Option: Use a manual bypass switch for the PCS1 power to manually turn the fan on

without activating the solar controller. This is useful for ventilating the attic without heating the

pool. An alternative method is to unplug the bypass valve’s valve operator [VOR] so it doesn’t

route water to the PCS1 and then turning the LX220 to ON[manual override]. This also turns the

fan on.

17. Use a pump manual bypass switch for manual pump operation.

18. DO NOT DIRECT WIRE THE PCS1.Use an outlet box in the attic so the unit

IMAGE PCS1_MANUAL55.gif

can be unplugged for service needs. Use a double pole cutoff switch for attic power as an

additional safety feature if desired.

19. Some pumps may be wired to run off 110 vac. The pump is usually the source of

power for the LX220 and PCS1. Check first to see if the pump is capable of running off of 220

vac. Most pumps can be simply “switched” at a rear panel to run off 110 or 220 vac. If the pump

can run off of 220 vac, we recommend that the pump be switched and that the power be rewired at

the circuit breaker panel from 110 to 220 vac. This simplifies the electrical wiring.

If the pump only runs off of 110 vac, this power can still be used to run the LX220.

However, a separate electrical run will have to be made to the LX220 from the power panel for

220-vac PCS1 power. This 220 vac is then run from the LX220 [from the power relay] up to the

PCS1. The LX220 power relay controls the PCS1!

SECTION 3 - INSTALLATION

Page S3-38

ELECTRICAL WIRING DIAGRAM

Electrical Wiring Diagram

SECTION 3 - INSTALLATION

Page S3-39

INTERNAL FLOAT WIRING

IMAGE PCS1_MANUAL70.gif

22 Gauge cable from
LX220 Solar Control

Attic 10K Ohm Thermistor
Temperature Sensor [at peak].

PCS1

Float Sensor's
White Wires

Wire
Nut

From LX220
SOL Terminals

NOTE: Not drawn to any scale

The attic based solar sensor [thermistor] must be wired “IN-SERIES” [in-line] with the leak detection float’s
white wires [AS SHOWN ABOVE]. The float is a closed circuit switch. If excess water should ever occur inside
the PCS1, the float rises and the switch opens. In AUTO mode, the LX220 interprets this open circuit condition as
a cold attic and shuts the bypass valve off. The LX220 “Solar Sensor Service Req’d” light will then turn ON
indicating a need for service.